main feature:
g) Configurable backup power supply (optional), the main power and backup power are automatically switched and the backup power working status icon is displayed intuitively in the menu bar;
h) The alarm channel number, alarm status and alarm time can be directly queried through the menu;
i) The short-distance RTU wireless transmission method or the unlimited-distance GPRS wireless transmission method can transmit real-time detection data and alarm status to the safety center through the built-in wireless module (optional);
The main function:
Alarm function
When the following situations occur, the controller will send out an audible and visual alarm signal:
a) When the measured gas concentration exceeds the set first-level (A1 low alarm) alarm value or second-level (A2 high alarm) alarm value, the buzzer will make continuous beeps, the concentration alarm indicator light is on, and the public relay is activated. combine;
b) When the controller is connected to the gas detector circuit and there is a failure, such as: no signal output, transmission line disconnection, transmission line short circuit, gas detector signal output exceeds the measurement range, the buzzer will beep continuously, and the fault alarm will be issued at the same time The indicator light is on, and the public relay is closed;
c) When the main power is cut off and the controller is powered by the backup power, the buzzer will beep briefly, and when the voltage of the backup power is insufficient, the buzzer will beep continuously.
Self-test function
Self-inspection when starting up, the controller automatically checks the functions of the indicator lights and buzzers on its panel. The instrument self-test menu can also perform functional self-test on the status indicator, buzzer and relay.
Data logging function
Through the menu, you can directly query historical data records and real-time curves, and you can customize the data saving interval. When the gas concentration of a certain channel exceeds the set alarm value, the alarm channel number, alarm concentration value and alarm time will be automatically recorded.
Parameter setting function
The working parameters of the controller can be viewed and modified at any time, including the current date/time, measurement range, resolution, alarm values at all levels, channel shielding, installation location, etc.
Main and backup power automatic switching function
When the main power supply of the controller is cut off, it can automatically switch to the backup power supply; when the main power supply is restored, it can automatically switch to the main power supply; the working status of the main and backup power supplies is indicated by an indicator light. When the main power supply is working, it can charge the backup power supply at the same time, and it will automatically turn to the floating charge state after the backup power is fully charged.
Alarm output control function
The controller has 2 public alarm output relays and 8 programmable alarm output relays. Equipment for controlling fire-fighting equipment, ventilation equipment, alarm equipment or other purposes. .
Current Calibration Function
The controller can calibrate the input current signals of 4mA, 12mA and 20mA to ensure timely synchronization of signals.
communication function
The controller has 3 RS-485 ports and 1 Ethernet port, which can easily transmit data to other control devices, computers, etc. The default address of the controller is: 5, and the baud rate is: 9600.
Other functions
Display of the total number of alarm channels, 4~20mA current signal output, etc.
Product parameters:
product name |
Gas Alarm Controller |
Product number |
AGP2100 |
Working power |
220VAC +10%, -15%; 50Hz ±5Hz |
fuse |
Rated current: 10A Size: 5mm*20mm |
Maximum working current |
1.5A (24VDC) |
backup power |
14.8VDC, 5.2AH (polymer lithium battery) |
output power |
24VDC, 1000mA |
Way of working |
Inspection |
input signal |
① 4~20mA current signal (three-wire gas detector) |
control channel |
① 4~20mA current signal split line type: support 1 channel to 32 channels |
output signal |
4~20mA current signal (optional) |
alarm record |
Alarm location display, alarm event record, time, concentration, etc. |
Alarm value setting |
A1 alarm value, A2 alarm value; interval alarm |
Alarm function |
LED indicator light and buzzer sound alarm |
Alarm Output |
2-way public relay output, 8-way programmable relay output |
Contact rating |
220VAC, 1A |
Communication Interface |
RS-485 MODBUS; 3 RS-485 ports and 1 Ethernet port |
Operating temperature |
-20°C - 55°C |
Working humidity |
0-95% relative humidity (non-condensing) |
Environmental pressure |
86~106kPa |
Display method |
7-inch or 9-inch touch TFT-LCD color LCD screen, 800x480 dot matrix LCD |
measurement accuracy |
≤±1% (current signal) |
shell material |
SPCC (optional 304 or 316 stainless steel) |
Dimensions |
Length 300mm x height 400mm x width 100mm |
weight |
about 6.5kg |
Alarm method |
Sound alarm 95 dB@30cm, red LED concentration indicator light, short-distance wireless and unlimited distance GPRS wireless alarm transmission mode |
button |
Touch operation, with the three-key operation of mute, lock screen, and flip screen |
direct reading |
Measured value, ambient temperature, humidity |
data record |
Automatic storage, can store 300,000 sets of data with date and time continuously, optional TF memory card, can store more than 10 million sets of data |
data download |
Support USB measurement data download; |
data transmission |
Support RTU wireless transmission or unlimited distance GPRS wireless transmission (optional) |
data printing |
Support micro data printer serial port printing |
calibration |
Support 4mA, 12mA, 20mA three-level current calibration operation |
degree of protection |
IP54 |
operating mode |
Two operating modes, user mode and administrator mode, are available |
Executive standard |
GB16808-2008 |